NB!
The keyboard/parameter database are blocked while Set-up Copy is running.
[0 ]
*
No Copy Copy function is inactive
[1] Copy from Set-up 1 Copy from
Set-up 1
to edit set-up chosen in par. 0-11,
Edit Set-up
.
[2] Copy from Set-up 2 Copy from
Set-up 2
to edit set-up chosen in par. 0-11,
Edit Set-up
.
[9] Copy from Factory Set-
up
Copy from Factory Settings to edit set-up chosen in par. 0-11,
Edit set-up
.
4.1.6. 0-6* Password
0-60 (Main) Menu Password
Range: Function:
Use password for protection against unintended change of sensitive parameters, eg. motor parameters.
Password protected parameters can always be read, but cannot be edited without entering the password.
0
*
[0 - 999]
Enter the password for access to Main Menu via the [Main Menu] key. Select the number that should allow for
changing other parameter values.
0
means there is no password.
NB!
A password only has affect on the LCP - not on the bus communication.
NB!
Pressing buttons [MENU], [OK] and down will unlock the password. This will automatically enter the parameter editing screen in Quick
Menu or Main Menu.
4. Parameter Descriptions VLT
p
Micro Drive FC 51
14
MG.02.C4.02 - VLT
p
is a registered Danfoss trademark
4