13-20 SL Controller Timer 0 s 1 set-up TRUE -2 Uint32
13-4* Logic Rules
13-40 Logic Rule Boolean 1 [0] False 1 set-up TRUE - Uint8
13-41 Logic Rule Operator 1 [0] Disabled 1 set-up TRUE - Uint8
13-42 Logic Rule Boolean 2 [0] False 1 set-up TRUE - Uint8
13-43 Logic Rule Operator 2 [0] Disabled 1 set-up TRUE - Uint8
13-44 Logic Rule Boolean 3 [0] False 1 set-up TRUE - Uint8
13-5* States
13-51 SL Controller Event [0] False 1 set-up TRUE - Uint8
13-52 SL Controller Action [0] Disabled 1 set-up TRUE - Uint8
5.2.14 14-** Special Functions
Param
eter #
Parameter description Default value 4 set-up Change during
operation
Conversion
index
Type
14-0* Inverter Switching
14-01 Switching Frequency ExpressionLimit All set-ups TRUE - Uint8
14-03 Overmodulation [1] On All set-ups FALSE - Uint8
14-07 Dead Time Compensation Level ExpressionLimit All set-ups FALSE 0 Uint8
14-08 Damping Gain Factor ExpressionLimit All set-ups TRUE 0 Uint8
14-09 Dead Time Bias Current Level ExpressionLimit All set-ups FALSE 0 Uint8
14-1* Mains On/O
14-10 Mains Failure [0] No function All set-ups FALSE - Uint8
14-11 Mains Voltage at Mains Fault ExpressionLimit All set-ups TRUE 0 Uint16
14-12 Function at Mains Imbalance [0] Trip 1 set-up TRUE - Uint8
14-15 Kin. Backup Trip Recovery Level ExpressionLimit All set-ups TRUE -3 Uint32
14-2* Reset Functions
14-20 Reset Mode [0] Manual reset All set-ups TRUE - Uint8
14-21 Automatic Restart Time 10 s All set-ups TRUE 0 Uint16
14-22 Operation Mode
[0] Normal
operation 1 set-up TRUE - Uint8
14-24 Trip Delay at Current Limit 60 s All set-ups TRUE 0 Uint8
14-25 Trip Delay at Torque Limit 60 s All set-ups TRUE 0 Uint8
14-27 Action At Inverter Fault [1] Warning All set-ups TRUE - Uint8
14-28 Production Settings [0] No action 1 set-up FALSE - Uint8
14-29 Service Code 0 N/A 1 set-up TRUE 0 Uint32
14-3* Current Limit Ctrl.
14-30 Current Lim Ctrl, Proportional Gain 100 % All set-ups TRUE 0 Uint16
14-31 Current Lim Ctrl, Integration Time 0.020 s All set-ups TRUE -3 Uint16
14-32 Current Lim Ctrl, Filter Time 5 ms All set-ups TRUE -4 Uint16
14-4* Energy Optimising
14-40 VT Level 66 % All set-ups FALSE 0 Uint8
14-41 AEO Minimum Magnetisation 66 % All set-ups FALSE 0 Uint8
14-44 d-axis current optimization for IPM 100 % All set-ups TRUE 0 Uint8
14-5* Environment
14-50 RFI Filter [2] Grid Type 1 set-up FALSE - Uint8
14-51 DC-Link Voltage Compensation [1] On All set-ups FALSE - Uint8
14-52 Fan Control
[5] Constant-on
mode 1 set-up TRUE - Uint8
14-55 Output Filter [0] No Filter 1 set-up FALSE - Uint8
14-6* Auto Derate
14-61 Function at Inverter Overload [0] Trip All set-ups TRUE - Uint8
14-63 Min Switch Frequency [2] 2.0 kHz 1 set-up FALSE - Uint8
Parameter Lists
VLT
®
Midi Drive FC 280
126 Danfoss A/S © 12/2015 All rights reserved. MG07C102
55