4 Parameter Descriptions
4.1 Parameters: 0-** Operation and Display
0-01 Language
Select the language to be used in the display.
Option: Function:
[0] * English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Spanish
[5] Italiano
0-03 Regional Settings
Option: Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0] * Interna-
tional
Activates parameter 1-20 Motor Power [kW] for
setting the motor power in kW and sets the
default value of parameter 1-23 Motor Frequency
to 50 Hz.
[1] US Activates parameter 1-20 Motor Power [kW] for
setting the motor power in hp and sets the
default value of parameter 1-23 Motor Frequency
to 60 Hz.
0-04 Operating State at Power-up (Hand)
Option: Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in hand on
mode.
[0] Resume Restarts the frequency converter, maintaining
the start/stop settings (applied by [Hand On/
O]) selected before the power-down of the
frequency converter.
[1] * Forced stop,
ref=old
Restarts the frequency converter with a saved
local reference after mains voltage reappears
and after pressing [Hand On].
[2] Forced stop,
ref=0
Resets the local reference to 0 upon
restarting the frequency converter.
0-06 GridType
Select the supply voltage, frequency, and type.
Option: Function:
[10] 380-440V/50Hz/IT-grid
[11] 380-440V/50Hz/Delta
[12] 380-440V/50Hz
[20] 440-480V/50Hz/IT-grid
0-06 GridType
Select the supply voltage, frequency, and type.
Option: Function:
[21] 440-480V/50Hz/Delta
[22] 440-480V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-grid
[121] 440-480V/60Hz/Delta
[122] 440-480V/60Hz
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast in IT
grid environment. This parameter is active only when
[1] On is selected in this parameter, and IT-grid options
are selected in parameter 0-06 GridType.
[0] O This function is not active.
[1] * On This function is active.
0-10 Active Set-up
Select the set-up to control the frequency converter functions.
Program parameters in set-ups 1–4. Use the factory set-up to
return the initial state. Use multi set-up for remote control.
Option: Function:
[1] * Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-up
0-11 Programming Set-up
Select the set-up to be programmed during operation; either the
active set-up or the inactive set-up. The set-up number being
edited ashes in the LCP.
Option: Function:
[1] Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] * Active Set-up
Parameter Descriptions Programming Guide
MG07C102 Danfoss A/S © 12/2015 All rights reserved. 23
4 4

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals