4 Parameter Descriptions
4.1 Parameters: 0-** Operation and Display
0-01 Language
Select the language to be used in the display.
Option: Function:
[0] * English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Spanish
[5] Italiano
0-03 Regional Settings
Option: Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0] * Interna-
tional
Activates parameter 1-20 Motor Power [kW] for
setting the motor power in kW and sets the
default value of parameter 1-23 Motor Frequency
to 50 Hz.
[1] US Activates parameter 1-20 Motor Power [kW] for
setting the motor power in hp and sets the
default value of parameter 1-23 Motor Frequency
to 60 Hz.
0-04 Operating State at Power-up (Hand)
Option: Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in hand on
mode.
[0] Resume Restarts the frequency converter, maintaining
the start/stop settings (applied by [Hand On/
O]) selected before the power-down of the
frequency converter.
[1] * Forced stop,
ref=old
Restarts the frequency converter with a saved
local reference after mains voltage reappears
and after pressing [Hand On].
[2] Forced stop,
ref=0
Resets the local reference to 0 upon
restarting the frequency converter.
0-06 GridType
Select the supply voltage, frequency, and type.
Option: Function:
[10] 380-440V/50Hz/IT-grid
[11] 380-440V/50Hz/Delta
[12] 380-440V/50Hz
[20] 440-480V/50Hz/IT-grid
0-06 GridType
Select the supply voltage, frequency, and type.
Option: Function:
[21] 440-480V/50Hz/Delta
[22] 440-480V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-grid
[121] 440-480V/60Hz/Delta
[122] 440-480V/60Hz
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast in IT
grid environment. This parameter is active only when
[1] On is selected in this parameter, and IT-grid options
are selected in parameter 0-06 GridType.
[0] O This function is not active.
[1] * On This function is active.
0-10 Active Set-up
Select the set-up to control the frequency converter functions.
Program parameters in set-ups 1–4. Use the factory set-up to
return the initial state. Use multi set-up for remote control.
Option: Function:
[1] * Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-up
0-11 Programming Set-up
Select the set-up to be programmed during operation; either the
active set-up or the inactive set-up. The set-up number being
edited ashes in the LCP.
Option: Function:
[1] Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] * Active Set-up
Parameter Descriptions Programming Guide
MG07C102 Danfoss A/S © 12/2015 All rights reserved. 23
4 4