To run AMA using the LCP
1. By default parameter setting, connect terminals
12 and 27 before running AMA.
2. Enter the Main Menu.
3. Go to parameter group 1-** Load and Motor.
4. Press [OK].
5. Set motor parameters using nameplate data for
parameter group 1-2* Motor Data.
6. Set motor cable length in parameter 1-42 Motor
Cable Length.
7. Go to parameter 1-29 Automatic Motor Adaptation
(AMA).
8. Press [OK].
9. Select [1] Enable complete AMA.
10. Press [OK].
11. The test runs automatically and indicates when it
is complete.
Depending on the power size, the AMA takes 3 to 10
minutes to complete.
NOTICE
The AMA function does not cause the motor to run and
it does not harm the motor.