3-95 Ramp Delay
Range: Function:
1000
ms*
[0 -
3600000 ms]
Enter the delay required from activation
of the digital potentiometer function
until the frequency converter starts to
ramp the reference. With a delay of 0 ms,
the reference starts to ramp as soon as
INCREASE/DECREASE is activated.
3-96 Maximum Limit Switch Reference
Enter the maximum limit switch reference. If the crane reaches a
limit switch (OFF), and if the speed exceeds the value in this
parameter, then the speed is reduced automatically to the value
in this parameter. If the limit switch is o, the speed cannot
exceed the value in this parameter.
Range: Function:
25 %* [0 - 200 %]
Parameter Descriptions Programming Guide
MG07C102 Danfoss A/S © 12/2015 All rights reserved. 47
4 4