VLT
®
Soft Starter Pocket Guide 29
A single soft starter can be used to control multiple motors, either in
sequence or in parallel, provided the soft starter is correctly selected
for the application.
Motors in sequence
For two or more motors in sequence, the soft starter must be capable
of bearing the total start duty.
Installation requires additional wiring, plus separate overload protec-
tion and line and bypass contactors for each motor. The additional
installation costs may be greater than the cost of individual soft
starters.
* This control method is complex and would require the use
of a PLC or smart relay.
Multiple motors: Can one soft starter be used
to control multiple motors?

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)