DKG-509 User Manual V-29 (23.08.2013)
- 25 -
The unit is able to send SMS messages in fuel theft or fuelling conditions.
These SMS messages are sent without creating visible fault condition.
These features are enabled by setting the program parameter Engine Parameters > Fuel
Consumption / Hour to a value other than 0%.
The Fuel Consumption / Hour parameter should be set to a value clearly greater than the
maximum fuel consumption of the engine.
If the fuel level measured from the sender input is decreased more than this parameter in 1
hour period, then a FUEL THEFT sms message is sent to programmed telephone numbers.
If the fuel level measured from the sender input is increased more than this parameter in 1
hour period, then a FUELLING sms message is sent to programmed telephone numbers.
The unit offers possibility of updating the firmware in the field. The firmware is updated through
the RS-232 serial port using Rainbow or a special DOS program.
The unit will go to firmware download mode with a special command from the PC program. In
download mode, the display of the unit will showDL-V1.00
During firmware update process, the progress is visible through a completion bar on the
screen.
The firmware update operation will take around 3 minutes.
After completion of the update a special command will set back the unit to normal operation
mode.
Volvo engines equipped with EMS-II engine control unit have the engine speed selectable
through the J1939 CANBUS. The unit offers the possibility to the user to switch between the primary
and secondary speed using the programming menu.
If the program parameter Volvo Speed Toggle is increased, the unit will freeze for a few
seconds and switch the engine to 1800 rpm, which is generally the secondary speed. When the
parameter is decreased, the speed is set to the primary speed, which is generally 1500 rpm.
Please note also that a fine adjustment of the engine speed in the ± 8 % range may be done
using the program parameter J1939 Speed Adjust.
The unit must be in OFF mode, otherwise the speed
switching will not be performed.
Daha önceki parametre değerlerine geri dönüş
mümkün değildir.
6.24. Changing the Default Engine Speed in Volvo Engines
6.23. Firmware Update
6.22. Fuel Theft / Fuelling Messages

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Datakom DKG-509 and is the answer not in the manual?

Datakom DKG-509 Specifications

General IconGeneral
BrandDatakom
ModelDKG-509
CategoryController
LanguageEnglish

Related product manuals