EasyManua.ls Logo

Datakom DKG-509 - 8. MODBUS COMMUNICATION; MODBUS Connection Options; MODBUS Registers

Datakom DKG-509
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DKG-509 User Manual V-29 (23.08.2013)
- 31 -
The unit offers the possibility of MODBUS communication via its RS232 serial port.
The connection to the MODBUS master may be done in 3 ways:
1) RS232 connection using directly the RS232 port provided.
2) RS422/485 connection using external RS422/485 converter.
3) Modem connection using external modem.
The MODBUS mode is activated by assigning a controller address to the unit using MODBUS
Address program parameter. The possible address range is 1 to 144. Setting the address to 0 will
disable the MODBUS mode and allow communication under RAINBOW protocol.
The MODBUS properties of the unit are:
-Data transfer mode: RTU
-Serial data: 9600 bps, 8 bit data, no parity, 1 bit stop
-Supported functions:
-Function 3 (Read multiple registers)
-Function 6 (Write single register)
Detailed description about the MODBUS protocol is found in the document “Modicon Modbus
Protocol Reference Guide”. The web address is: www.modbus.org/docs/PI_MBUS_300.pdf
Below is a limited shortlist of readable registers. For the detailed Modbus Application
Manual and a complete list of registers please contact DATAKOM.
ADDRESS
(hex)
R /
W
DATA
SIZE
COEFFICIENT
DESCRIPTION
0000
R
16bit
x1
Mains Phase L1 voltage
0001
R
16bit
x1
Mains Phase L2 voltage
0002
R
16bit
x1
Mains Phase L3 voltage
0003
R
16bit
x1
Genset Phase L1 voltage
0004
R
16bit
x1
Genset Phase L2 voltage
0005
R
16bit
x1
Genset Phase L3 voltage
0006
R
16bit
x1
Genset Phase L1 current
0007
R
16bit
x1
Genset Phase L2 current
0008
R
16bit
x1
Genset Phase L3 current
000C
R
16bit
x1
Mains Phase L12 voltage
000D
R
16bit
x1
Mains Phase L23 voltage
000E
R
16bit
x1
Mains Phase L31 voltage
000F
R
16bit
x1
Genset Phase L12 voltage
0010
R
16bit
x1
Genset Phase L23 voltage
0011
R
16bit
x1
Genset Phase L31 voltage
0012
R
16bit
x10
Mains frequency
0013
R
16bit
x10
Genset frequency
0016-0017
R
32bit
x256
Genset active power: this 24 bit signed register holds
the genset active power multiplied by 256. Least
significant 16 bits are in the register 0016h. Most
significant 8 bits are in the LSB of the register 0017h.
0018
R
8bit
x100
Power factor multiplied by 100 (signed byte). Negative
values indicate a capacitive power factor.
002A
R
16bit
x1
Engine speed (rpm)
002B
R
16bit
x10
Oil pressure in bars.
002C
R
16bit
x1
Coolant temperature in degrees C.
002D
R
16bit
x1
Fuel level as %
002F
R
16bit
x10
Battery voltage
003D
R
8bit
-
Operating mode
bit_3: manual mode
bit_4: auto mode
bit_5: off mode
bit_6: test mode
bit_7: load test mode
8. MODBUS COMMUNICATION

Related product manuals