What to do if the trigger LED is not blinking in One Shot or Phase Mode using the External Trigger on Datalogic Industrial Equipment?
- PpatrickchapmanDec 1, 2025
If the "TRIGGER" LED is not blinking while the External Trigger is switching in One Shot or Phase Mode using Input 1 (External Trigger) or Input 2 on your Datalogic Industrial Equipment, check the following: Determine if you're referring to the 17-pin connector or the CBX spring clamp connectors. Verify if the sensor is connected to Input 1 or Input 2. Ensure power is supplied to the photo sensor. For NPN configuration, check if power is supplied to one of the two I1 or I2 signals (A or B). For PNP configuration, verify if one of the two I1 or I2 signals is grounded (A or B). Check if the photo sensor LEDs (if any) are working correctly. Ensure the sensor/reflector system is aligned (if present). On the Reading Phase step, check the Input 1 or Input 2 Debouncing Time parameter setting. Als...