For wiring details, please refer to "Wiring instructions" in this section.
In case of very long lines on the network, terminating resistors might be needed (typically 120
Ω 1 %, 0.5 W).
The calculation should be based on the following data:
A line internal pull-up bias resistor: 22 kΩ
B line internal pull-down bias resistor: 22 kΩ
Receiver input sensitivity: +/-200 mV
Receiver input impedance: 12 kΩ