Installation Section 2
SELFCONTAINED REFRIGERATED DROPIN UNITS
8100-EFNP, N8100BP
For any non-standard installation consult the factory.
1. Install a GFCI receptacle a minimum of 14” (36cm) up
from the cabinet bottom inside the partitions. We
recommend installing a remote located power switch
for ease of use.
2. Cabinet interior minimum dimensions:
Dimension 8148-EFNP N8168-EFNP 8191-EFNP
A 46.87"/199cm 68.5"/174cm 90"/229cm
B 19"/48cm 19"/48cm 19"/48cm
C 26"/66cm 26"/66cm 26"/66cm
D 45.75/116cm 66.5"/169cm 90"/229cm
E 17.25"/44cm 17.25"/44cm 17.25"/44cm
F Min. 2.75”/7cm - Max. 4.75”/12cm
Dimension N8118BP N8130BP N8143BP
A 22.38"/57cm 29.75"/76cm 42.5"/108cm
B 27.75"/70cm 27.75"/70cm 27.75"/70cm
C 26"/66cm 26"/66cm 26"/66cm
D 17"/43cm 29.75"/76cm 42.5"/108cm
E 25"/64cm 25"/64cm 25"/64cm
F Min. 2.75”/7cm - Max. 4.75”/12cm
Dimension N8156BP N8169BP N8181BP
A 55.25"/140cm 68"/173cm 80.75"/205cm
B 27.75"/70cm 27.75"/70cm 27.75"/70cm
C 26"/66cm 26"/66cm 26"/66cm
D 55.25"/140cm 68"/173cm 80.75"/205cm
E 25"/64cm 25"/64cm 25"/64cm
F Min. 2.75”/7cm - Max. 4.75”/12cm
3. Place the condensing unit through the counter cutout.
4. Extend the telescoping duct from the front of the
condensing unit to the back of the louver. This will
prevent recirculation of discharge air. Export models do
not have a telescoping duct, skip to step 6.
5. Put eight provided screws through the telescoping
duct side walls to hold it at the desired depth.
22.50”
(57cm)
C
E
D
A
B
11.50”
(29cm)
F
Use Screws to Secure Desired Depth
3 of 8 Screws Shown
6. Partitions must fully extend front to back and top to
bottom.
7. Louver cutout must extend to bottom of cabinet and
align with condenser face.
NOTE: The louver provided must be installed in front of