24 Part Number: 9291458 REV00 12/19
Installation Section 2
SELFCONTAINED REFRIGERATED DROPIN UNITS
8200P, N8200-GP, N8200-STP
For any non-standard installation consult the factory.
1. Install a GFCI receptacle a minimum of 14” (36cm) up
from the cabinet bottom inside the partitions. We
recommend installing a remote located power switch
for ease of use
2. Cabinet interior minimum dimensions:
Dimension N8231P/GP N8245P/GP N8259P/GP
A 30.75"/78cm 44.25"/112cm 58.5"/149cm
B 27.75"/70cm 27.75"/70cm 27.75"/70cm
C 26"/66cm 26"/66cm 26"/66cm
D 30.75"/78cm 44.25"/112cm 58.5"/149cm
E 25"/64cm 25"/64cm 25"/64cm
F Min. 2.75”/7cm - Max. 4.75”/12cm
Dimension N8273P/GP N8287P/GP
A 72.38"/184cm 86.25"/219cm
B 27.75"/70cm 27.75"/70cm
C 26"/66cm 26"/66cm
D 72.38"/184cm 86.25"/219cm
E 25"/64cm 25"/64cm
F Min. 2.75”/7cm - Max. 4.75”/12cm
Dimension N8230-STP N8240-STP N8256-STP
A 28.6"/73cm 38.65"/98cm 54.6"/139cm
B 27.75"/70cm 27.75"/70cm 27.75"/70cm
C 26"/66cm 26"/66cm 26"/66cm
D 30.75"/78cm 44.63"/113cm 58.5"/149cm
E 21.12"/54cm 28.75"/73cm 21.12"/54cm
F Min. 2.75”/7cm - Max. 4.75”/12cm
Dimension N8258-STP N8275-STP
A 56.6"/144cm 74.5"/189cm
B 27.75"/70cm 27.75"/70cm
C 26"/66cm 26"/66cm
D 72.38"/184cm 86.25"/219cm
E 28.75"/73cm 28.75"/73cm
F Min. 2.75”/7cm - Max. 4.75”/12cm
3. Place the condensing unit through the counter cutout.
4. Extend the telescoping duct from the front of the
condensing unit to the back of the louver. This will
prevent recirculation of discharge air. Export models do
not have a telescoping duct, skip to step 6.
22.50”
(57cm)
C
E
D
A
B
11.50”
(29cm)
F
5. Put eight provided screws through the telescoping
duct side walls to hold it at the desired depth.