Figure 7 Power distribution cabling — DLm8500
Power and cooling data
This section provides an overview of power and cooling data.
The following table provides details of power consumption and heat dissipation for
maximally configured DLm8500 Multiple Rack Solution systems (containing eight
VTEs, two 10 GbE data switches, and two 1 GbE management switches):
Table 10
DLm8500 Multiple Rack Solution power consumption and heat dissipation
System configuration
description
a
Total power consumption
(kVA)
Heat dissipation
(Btu/Hr)
VTEC cabinet 3.70 12,300
External DD6800, DD9300,
DD9800 cabinet
4.76 15,000
External DD6300 4.16 12,100
External Data Domain DAE
storage cabinet
3.36 9600
a.
All cabinet values are calculated for a fully loaded configuration. Contact your Dell EMC
Sales Representative for specific supported configurations.
The following table provides details of power consumption and heat dissipation for
maximally configured DLm8500 Multiple Rack Solution systems (containing two VTEs,
two 10 GbE data switches, and two 1 GbE management switches):