DLm power requirements
This section describes the North American electrical specifications, power cables,
connectors, and extension cords for the VTEC cabinet in a DLm configuration.
The
Dell EMC PowerMax Family Site Planning Guide
provides further information about
power requirements for PowerMax system and storage cabinets.
The following table summarizes the North American, single-phase, electrical
specifications power requirements specific to a single VTEC cabinet:
Table 16 North American, single-phase, electrical specifications
Specification Requirements
Input voltage 200 V AC to 240 V AC -10%/+10% single-phase
Frequency 50 Hz to 60 Hz
Circuit breakers 30 A
Power zones Two
Power requirements at customer site (for each
cabinet)
Two single-phase drops each for: DLm8500 VTEC cabinet
with up to one fully loaded
Power distribution panel connectors NEMA L6-30P, and the Facility power mating receptacle
is L6-30R.
Before delivery, the customer must supply and install the required receptacles to zone
A and zone B power for the DLm cabinets. The following figure shows the required
power cabling for DLm8500 systems:
DLm8500 with PowerMax Physical Planning
38 Disk Library for mainframe Physical Planning Guide for DLm8500