Table 20. Supported video resolution options
Resolution Refresh rate (Hz) Color depth (bits)
1024 x 768 60 8, 16, 32
1280 x 800 60 8, 16, 32
1280 x 1024 60 8, 16, 32
1360 x 768 60 8, 16, 32
1440 x 900 60 8, 16, 32
1600 x 900 60 8, 16, 32
1600 x 1200 60 8, 16, 32
1680 x 1050 60 8, 16, 32
1920 x 1080 60 8, 16, 32
1920 x 1200 60 8, 16, 32
Environmental specifications
NOTE:
For additional information about environmental certifications, refer to the P
roduct Environmental Datasheet located
with the Documentation on www.dell.com/support/home.
Table 21. Continuous Operation Specifications for ASHRAE A2
Description Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
29
53 ft)
10–35°C (50–95°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/300 m (33.8°F/984 Ft) above
900 m (2953 Ft)
Table 22. Continuous Operation Specifications for ASHRAE A3
Description Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2
9
53 ft)
5–40°C (41–104°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/175 m (33.8°F/574 Ft) above
900 m (2953 Ft)
Table 23. Continuous Operation Specifications for ASHRAE A4
Description Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
29
53 ft)
5–45°C (41–113°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/125 m (33.8°F/410 Ft) above
900 m (2953 Ft)