Chapter 5 Communication Interfaces
25
z
z
Alarm
When any external battery pack connected to the UPS has the following
problems, the UPS system will sound an alarm. Please see the table below.
No.
External Battery
Pack Status
Description
1 Battery Mode The alarm beeps once every 2 seconds.
2 Battery Low Warning The alarm beeps once every 0.5 second.
3
Battery Missing/
Weak Battery/ Battery
Replacement
The alarm beeps once every 2 seconds.
4 Overload
1. Overload_105%~125%: The alarm beeps
once every 2 seconds.
2. Overload_125%~150%: The alarm beeps
once every 0.5 second.
5 Fault
The alarm beeps continuously for 5 seconds
when the UPS detects an internal fault. After
the 5-seconds long beep, the alarm beeps
once every 2 seconds.
NOTE :
*: After reconnecting or replacing the batteries, it might take a while for
the UPS to switch o󰀨 the alarm automatically. If, after a period of time, the
audible alarm still exists, please manually initiate a battery test. Please
follow the route below to execute the manual battery test in order to clear
the alarm.
Route: press the button
for 0.1 second → tap the icon
Maintenance
→ select
Testselect Start Battery Test. Fore relevant information, please refer
to 9.2 Main Menu.