EasyManua.ls Logo

Delta Amplon Series - Page 42

Delta Amplon Series
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Amplon RT Series
UPS
Suggested Backfeed
Protection Device
Rating Voltage/ Current
Suggested Model
No.
8/ 10kVA
208/ 220/ 230/ 240Vac
65A
AF52-30-13 (ABB)
z
z
Control Relay Requirements:
Breaking Capacity 240Vac/ 5A
Contact Form Normally Closed (NC)
Coil 12Vdc/ <0.5A
Suggested Model No. HF13F-012-1Z1T
z
z
Backfeed Protection Wiring Diagram:
Please refer to the diagram below to install the backfeed protection device
between the AC input and the UPS.
L (L1)
N (L2)
L (L1)
N (L2)
UPS
Coil
Control Relay
Contactor
Dry
Contact
DC 12V

Other manuals for Delta Amplon Series

Related product manuals