Chapter 5  Trial operation and Tuning  ASDA-A2 
5-4  Revision February, 2017 
3)  When the screen displays: 
 
Warning of emergency stop: 
Please check if any of the digital input DI1~DI8 is set to emergency stop (EMGS). 
Corrective action: 
   If not desire to set emergency stop (EMGS) as one of the digital input, make sure no 
digital input is set to emergency stop (EMGS) among DI1~DI8. (That is to say none of 
the parameters, P2-10~P2-17 is set to 21.) 
  If the function of emergency stop (EMGS) is needed and this DI is set as normally 
close (function code: 0x0021), please make sure this DI is always normally close. If 
not, please set this DI as normally open (function code: 0x0121).  
4)  When the screen displays: 
 
Warning of negative limit error: 
Please check if any of the digital input DI1~DI8 is set to negative limit (NL) and that DI is 
ON. 
Corrective action: 
   If not desire to set negative limit (NL) as one of the digital input, make sure no  digital 
input is set to negative limit (NL) among DI1~DI8. (That is to say none of the 
parameters, P2-10~P2-17 is set to 22.) 
  If the function of negative limit (NL) is needed and this DI is set as normally close 
(function code: 0x0022), please make sure this DI is always normally close. If not, 
please set this DI as normally open (function code: 0x0122). 
 
5)  When the screen displays: 
 
 
Warning of positive limit error: 
Please check if any of the digital input DI1~DI8 is set positive limit (PL) and that DI is ON. 
Corrective action: 
  If not desire to set positive limit (PL) as one of the digital input, make sure no digital 
input is set to positive limit (PL) among DI1~DI8. (That is to say none of the 
parameters, P2-10~P2-17 is set to 23.) 
  If the function of positive limit (PL) is needed and this DI is set as normally close 
(function code: 0x0023), please make sure this DI is always normally close. If not, 
please set this DI as normally open (function code: 0x0123).