ASDA-A2  Chapter 8  Parameters 
Revision February, 2017    8-45 
 
 
Torque Output Direction Settings   
  0  1 
Forward 
 
 
Reverse 
 
 
 
  Digital Input / Digital Output (DIO) Setting 
0: When switching mode, DIO (P2-10 ~ P2-22) remains the 
original setting value and will not be changed. 
1: When switching mode, DIO (P2-10 ~ P2-22) can be reset to the 
default value of each operational mode automatically. 
 
P1-02▲ 
 
PSTL  Speed and Torque Limit Setting 
Address: 0104H 
0105H 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section: 
Section 6.6 
Table 8.1 
 
Default: 
0 
 
Control 
Mode: 
ALL 
 
Unit: 
- 
 
Range: 
00 ~ 0x11 
 
Data Size: 
16-bit 
 
Format: 
Hexadecimal 
 
Settings: 
 
 
   Disable / enable speed limit function 
0: Disable speed limit function 
1: Enable speed limit function (it is effective in T / Tz mode only) 
Other: Reserved 
Block diagram of speed limit setting: 
Disable / enable speed limit function
Not in use
Disable / enable torque limit function