Chapter 9 Communications  ASDA-A2 
Revision February, 2017     9-5 
P3-02    PTL  Communication Protocol 
Address: 0304H 
0305H 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section:  
9.2 
 
Default: 
6 
 
Control 
Mode: 
ALL 
 
Unit: 
- 
 
Range: 
0 ~ 0x8 
 
Data Size: 
16-bit 
 
Format: 
Hexadecimal 
 
Settings: 
The definition of the setting value is as the followings: 
0: 7, N, 2 (MODBUS, ASCII) 
1: 7, E, 1 (MODBUS, ASCII) 
2: 7, O,1 (MODBUS, ASCII) 
3: 8, N, 2 (MODBUS, ASCII) 
4: 8, E, 1 (MODBUS, ASCII) 
 
 
5: 8, O, 1 (MODBUS, ASCII) 
6: 8, N, 2 (MODBUS, RTU) 
7: 8, E, 1 (MODBUS, RTU) 
8: 8, O, 1 (MODBUS, RTU) 
 
P3-05    CMM  Communication Mechanism 
Address: 030AH 
030BH 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section:  
9.2 
 
Default: 
0 
 
Control 
Mode: 
ALL 
 
Unit: 
- 
 
Range: 
0x00 ~ 0x01 
 
Data Size: 
16-bit 
 
Format: 
Hexadecimal 
 
Settings: 
Communication port can select one or more than one communications. 
 Communication Interface 
0: RS232 
1: RS485