3 Mixed Analog Input/Output Module DVP06XA-E2
For voltag
e input Mode0/Mode2: 0.3125mV = 20V/64,000 = 10V/32,000
Equation:

OffsetGain
Offset
V
VX
Y

32000
)(10
)(
16000
Y=Digital value, X=Voltage input
For voltage input Mode1/Mode3: 0.15625mV
= 10V/64,000 = 5V/32,000
Equation:

OffsetGain
Offset
V
VX
Y

32000
)( 5
)(
16000
Y=Digital value, X=Voltage input
For current input Mode4/Mode5: 0.625A = 40mA/64,000 = 20mA/32,000
Equation:

OffsetGain
Offset
mA
mAX
Y

32000
)(20
)(
16000
Y=Digital value, X= Current input
For current input Mode6: 0.5A = 16mA/32,000
Adopt the equation of current input mode4/mode5, substitute Gain for 19,200(12mA) and Offset for
6,400(4mA)
Equation:

640019200
640032000
)(20
)(
16000

mA
mAX
Y
Y=Digital value, X= Current input
1. Voltage input mode
Mode 0 (H0000): (-10V ~ +10V)
Voltage input
+32000
+16000
-16000
10V
-32000
-10V
5V
0
Gain
Offset
Digital
output
+32384
-32384
Mode 0 of CR#2~ CR#5 -10V ~ +10V, Gain = 5V (16,000), Offset = 0V (0).
Gain (CR#34 ~ CR#37) The voltage input value corresponds to digital value 16,000.
Offset (CR#28 ~ CR#31) The voltage input value corresponds to digital value 0.
Range of digital conversion -32,000 ~ +32,000
Max./Min. output range of digital data -32,384 ~ +32,384
DVP-ES2 Module Manual
3-12

Table of Contents

Other manuals for Delta DVP-ES2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-ES2 and is the answer not in the manual?

Delta DVP-ES2 Specifications

General IconGeneral
BrandDelta
ModelDVP-ES2
CategoryController
LanguageEnglish

Related product manuals