EasyManuals Logo

Delta DVP-EX2 User Manual

Delta DVP-EX2
1006 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #952 background imageLoading...
Page #952 background image
Appedndix B Setting and Using an Ethernet PLC/Module
B-19
DVP26SE: (0x352)
Instance
Attribute
Name
Access
Data Type
1
0
D0
Set
INT
1
1
D1
Set
INT
……
1
11999
D11999
Set
INT
(10) TCP/IP Interface Object (0xF5)
Instance: 0x01
Attribute
Name
Access
Data Type
Value
0x01
Status
Get
DWORD
0x00000001UL
0x02
Configuration
Capability
Get DWORD
DVP12SE =
0x00000014UL
(DHCP client,
Configuration Settable)
ES2-E & DVP26SE =
0x00000015UL
(DHCP client, BOOTP
Client, Configuration
Settable)
0x03
Configuration
Control
Get DWORD
Static IP: 0U
BOOTP: 0x01U(ES2-E
Only)
DHCP: 0x02U
0x04
Physical Link
Object:
Get
STRUCT of:
Path Size
UINT
Path
Padded EPATH
0x05
Interface
Configuration:
Set
STRUCT of:
IP Address UDINT
Network Mask UDINT
Gateway Address
UDINT
Name Server UDINT
Name Server 2 UDINT
Domain Name STRING
0x06
Host Name
Get
STRING
DVP12SE or ES2-E
0x0D
Encapsulation
Inactivity Timeout
Set
UINT
Keep Alive Timeout
120 s

Table of Contents