Communication Module DVPSCM12/52-SL
DVP-PLC Operation Manual
18
After double-clicking the added item, the user can edit the parameter.
Master:
PLC Type: It displays the PLC type. The user can click “Tools” in SCMSoft to change the
PLC type.
Data: Enter the address of the data register in the PLC to store the value read from
the slave.
Description:
Enter the description of the device. The maximum length is 30 bytes.
Salve:
Slave ID:
The number of the salve device from which the data is read
Device Type: The user can choose the Delta PLC type. If the PLC used is not a Delta PLC,
please leave the column blank.
Length (bit):
It indicates the length of the data being read. The maximum length is 100 bits.
Data Type: The user can choose either “Hex” or “Modbus 6 Digit”. “Hex” represents 6
hexadecimal digits, and “Modbus 6 Digit” represents 6 decimal digits. If the
device type is a Delta PLC type, the data type in this column will automatically
become the data register.
Start Address:
The start address of the data