Communication Module DVPSCM12/52-SL
DVP-PLC Operation Manual
61
7.4 BACnet MS/TP Slave Function (Supported by DVPSCM52-SL)
Set the BACnet parameters and the BACnet object for the SCM module, and then download them to the
SCM module to connect to the BACnet MS/TP module.
【BACnet parameters】
BACnet MAC address: 1 ~ 247 (Default: 247). It can not be the same as the address of other device on the
BACnet network.
Baud rate: 1200 bps~460800 bps (Default: 9600). It must be the same as the setting for the BACnet MS/TP
MPU.
Physical Type: The user can select RS-485 or RS-422.