5.2.8.4. Constant cosphi
此模式啟動後,逆變器可饋入固定功率因子(cosphi)之虛功功率至市電,
使用者可透過設定頁面指定欲饋入之功率因子。
5.2.8.5. Cosphi (P)
此功能啟動後,逆變器可隨著輸出之實功功率高低而饋入一定比例之虛功
功率。當國家設定為Italy LV或Italy MV時,使用者可進一步指定當市電
電壓高於V lock-in時方饋入虛功,電壓低於V lock-out後,無論此時輸出
實功功率為何,皆不饋入虛功。
Constant cosphi
Cosphi (P)
Constant Q
Q(V)
ENT
EXIT
Mode
cosphi
OFF
Ind 1.00
圖5-23 Constant cosphi頁面
圖5-24 Cosphi (P)頁面
Constant cosphi
Cosphi (P)
Constant Q
Q(V)
ENT
EXIT
EXIT
Mode
Q upper
P lower
Q lower
OFF
Ind 1.00
45%
Ind 0.90
P upper
V lock-in
V lock-out
90%
241.5V
230.0V
Q upper
Q lower
P/Pn
1
cosφ
P lower P upper
圖5-25 Cosphi (P)參數對照
203