Chapter 11 Summary of Parameter SettingsCFP2000 Series
When Pr.00-25 bit 0~3=0000B
Setting: 1~65535
0: Disable
When Pr.00-25 bit 0~3=0000B
Setting: 0.1~6553.5
Factory Setting: 0.0
When Pr.00-25 bit 0~3=0000B
Setting: 0.01~655.35
Factory Setting: 0.00
When Pr.00-25 bit 0~3=0000B
Setting: 0.001~65.535
Factory Setting: 0.000
Switch from AUTO control to HAND
(MANUAL) control
bit0: Sleep mode control bit
0: Disable sleep mode
1: Same sleep mode as in AUTO control
bit1: Unit displaying control bit
0: Change the displayed unit to Hz
1: Same unit displaying as in AUTO control
bit2: PID control bit
0: Disable PID mode
1: Same PID mode as in AUTO control
bit3: Source of frequency control bit
0: Source of the frequency depends on the
parameter setting. If the multi-speed
setting is enabled, the multi-speed has the
priority.
1: Source of frequency follows the setting of
Pr00-30, regardless the multi-speed
setting.
0: Standard HOA function
1: Switching Local/Remote, the drive stops
2: Switching Local/Remote, the drive runs as the
REMOTE setting for frequency and operation
status
3: Switching Local/Remote, the drive runs as the
LOCAL setting for frequency and operation
status
4: Switching Local/Remote, the drive runs as
LOCAL setting when switch to Local and runs as
REMOTE setting when switch to Remote for
frequency and operation status.
Source of the Master Frequency
Command(HAND)
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
Source of the Operation Command
(HAND)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP
disabled.
3: CANopen communication card
5: Communication card (not include CANopen card)