Chapter 11 Summary of Parameter SettingsCFP2000 Series
11-28
Pr.
Explanation
Settings
Factory
Setting
14: Error state
09-43
Reserved
09-44
Reserved
09-45
CANopen Master Function
0: Disable
1: Enable
0
09-46
CANopen Master Address
0~127
100
09-47
~
09-49
Reserved
09-50
BACnet Dnet
0~127
10
09-51
BACnet Baud Rate
9.66~76.8 kbps
38.4
09-52
BACnet Device ID L
0~65535
10
09-53
BACnet Device ID H
0~63
0
09-54
Reserved
09-55
BACnet Max Address
0~127
127
09-56
BACnet Password
0~65535
0
09-57
~
09-59
Reserved
09-60
Identifications for
Communication Card
0: No communication card
1: DeviceNet Slave
2: Profibus-DP Slave
3: CANopen Slave/Master
4: Modbus-TCP Slave
5: Ethernet/IP Slave
6~8: Reserved
0
09-61
Firmware Version of
Communication Card
Read only
##
09-62
Product Code
Read only
##
09-63
Error Code
Read only
##
09-64
~
09-69
Reserved
09-70
Address of Communication Card
(for DeviceNet and PROFIBUS)
DeviceNet: 0-63
Profibus-DP: 1-125
1
09-71
Setting of DeviceNet Speed
(for DeviceNet and PROFIBUS)
Standard DeviceNet:
0: 125Kbps
1: 250Kbps
2: 500Kbps
3: 1Mbps (Delta Only)
Nonstandard DeviceNet: (Delta Only)
0: 10Kbps
1: 20Kbps
2: 50Kbps
3: 100Kbps
4: 125Kbps
5: 250Kbps
6: 500Kbps
7: 800Kbps
8: 1Mbps
2
09-72
Other Setting of DeviceNet
Speed
(for DeviceNet and PROFIBUS)
0: Disable
In this mode, baud rate can only be 123K bps, 250K
bps, 500K bps in standard DeviceNet speed
1: Enable
In this mode, the baud rate of DeviceNet can be
same as CANopen (0-8).
0