Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-10
010xh: ft/m
011xh: m
012xh: ft
013xh: degC
014xh: degF
015xh: mbar
016xh: bar
017xh: Pa
018xh: kPa 019xh: mWG
01Axh: inWG
01Bxh: ftWG
01Cxh: psi
01Dxh: atm
01Exh: L/s
01Fxh: L/m
020xh: L/h
021xh: m3/s
022xh: m3/h
023xh: GPM
024xh: CFM
Bit 0~3: Control F page, unit of user defined value (Pr00-04 =d10, PID feedback) and the
decimal point of Pr00-26 which supports up to 3 decimal points.
Bit 4~15: Control F page, unit of user defined value (Pr00-04=d10, PID feedback) and the display
units of Pr00-26.
0
0
0 h
0
0:no decimal place
1:one
2:tw
3:three
decimal place
o decimal place
decimal place
0: Hz
1: rpm
2: %
3: kg
user defined decimal place
user defined unit
Max. User Defined Value
Factory Setting: 0
Settings 0: Disable
1~65535 (when Pr.00-25 set to no decimal place)
0.1~6553.5 (when Pr.00-25 set to 1 decimal place)
0.01~655.35 (when Pr.00-25 set to 2 decimal place)
0.001~65.535 (when Pr.00-25 set to 3 decimal place)
When Pr.00-26 is NOT set to 0. The user defined value is enabled. The value of this
parameter should correspond to the frequency setting at Pr.01-00.
Example:
When the frequency at Pr. 01-00=60.00Hz, the max. user defined value at Pr. 00-26 is 100.0%.
That also means Pr.00-25 is set at 0021h to select % as the unit.
NOTE
The drive will display as Pr.00-25 setting when Pr.00-25 is properly set and Pr.00-26 is not 0.