Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-11
User Defined Value
Factory Setting: Read only
Settings Read only
Pr.00-27 will show user defined value when Pr.00-26 is not set to 0.
Switching from Auto mode to Hand mode
Factory Setting: 0
Settings bit0: Sleep Function Control Bit
0: Sleep Function Control Bit
1: Sleep function and Auto mode are the same
bit1: Unit of the Control Bit
0: Displaying Unit in Hz
1: Same unit as the Auto mode
bit2: PID Control Bit
0: Cancel PID control
1: PID control and Auto mode are the same.
bit3: Frequency Source Control Bit
0: Frequency command set by parameter, if the multi-step speed is
activated, then multi-step speed has the priority.
1: Frequency command set by Pr00-30, regardless if the multi-speed is
activated.
LOCAL/REMOTE Selection
Factory Setting: 0
Settings 0: Standard HOA function
1: Switching Local/Remote, the drive stops
2: Switching Local/Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switching Local/Remote, the drive runs as the LOCAL setting for frequency
and operation status
4: Switching Local/Remote, the drive runs as LOCAL setting when switch to
Local and runs as REMOTE setting when switch to Remote for frequency
and operation status.
The factory setting of Pr.00-29 is 0 (standard Hand-Off-Auto function). The AUTO frequency and
source of operation can be set by Pr.00-20 and Pr.00-21, and the HAND frequency and source of
operation can be set by Pr.00-30 and Pr.00-31. AUTO/HAND mode can be selected or switched
by using digital keypad (KPC-CC02) or setting multi-function input terminal MI= 41, 42.
When external terminal MI is set to 41 and 42 (AUTO/HAND mode), the settings
Pr.00-29=1,2,3,4 will be disabled. The external terminal has the highest priority among all
command, Pr.00-29 will always function as Pr.00-29=0, standard HOA mode.
When Pr.00-29 is not set to 0, Local/Remote function is enabled, the top right corner of digital
keypad (KPC-CC02) will display “LOC” or “REM”. The LOCAL frequency and source of operation
can be set by Pr.00-20 and Pr.00-21, and the REMOTE frequency and source of operation can
be set by Pr.00-30 and Pr.00-31. Local/Remote function can be selected or switched by using
digital keypad (KPC-CC02) or setting external terminal MI=56. The AUTO key of the digital
keypad now controls for the REMOTE function and HAND key now controls for the LOCAL
function.