Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-12
disabled.
When MI is set to 56 for LOC/REM selection, if Pr.00-29 is not set to 0, the external terminal has
the highest priority of command and the ATUO/HAND keys will be disabled.
Source of the Master Frequency CommandHAND
Factory Setting: 0
Settings 0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
It is used to set the source of the master frequency in HAND mode.
Source of the Operation Command (HAND)
Factory Setting: 0
Settings 0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication card
5: Communication card (not include CANopen card
It is used to set the source of the operation frequency in HAND mode.
Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC02 or multi-function input
terminal (MI).
The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal
used to switch AUTO/HAND mode. The highest priority is the multi-function input terminal. When
the external terminal is OFF, the drive won’t receive any operation signal and can’t execute JOG.
Digital Keypad STOP Function
Factory Setting: 0
Settings 0: STOP key disable
1: STOP key enable
This parameter works when the source of operation command is not digital keypad (Pr00-210).
When Pr00-21=0, the stop key will not follow the setting of this parameter.
~
Reserved