Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-01-1
01 Basic Parameters This parameter can be set during operation.
Maximum Output Frequency
Factory Setting: 60.00/50.00
Settings 50.00~599.00Hz
Setting Range for /including 90kW(125HP) and above: 0.00~400.00Hz
This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC motor
drive frequency command sources (analog inputs 0 to +10V, 4 to 20mA, 0 to 20mA) are scaled to
correspond to the output frequency range.
Setting Range for /including 90kW(125HP) and above: 0.00~400.00Hz
Minimum Carrier Wave Requirement
Maximum Output Frequency
IM VF/ IM SVC
2k 200 Hz
3k 300 Hz
4k 400 Hz
5k 500 Hz
6k 599 Hz
Output Frequency of Motor 1(base frequency and motor rated frequency)
Output Frequency of Motor 2(base frequency and motor rated frequency)
Factory Setting: 60.00/50.00
Settings 0.00~599.00Hz
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it should be set
to 50Hz.
Output Voltage of Motor 1(base frequency and motor rated frequency)
Output Voltage of Motor 2(base frequency and motor rated frequency)
Factory Setting: 400.0
Settings series: 0.0~510.0V
This value should be set according to the rated voltage of the motor as indicated on the motor
nameplate. If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be set
to 200.0.
There are many motor types in the market and the power system for each country is also
difference. The economic and convenience method to solve this problem is to install the AC
motor drive. There is no problem to use with the different voltage and frequency and also can
amplify the original characteristic and life of the motor.
Mid-point Frequency 1 of Motor 1
Factory Setting: 3.00
Settings 0.00~599.00Hz
Mid-point Voltage 1 of Motor 1
Factory Setting: 22.0