EasyManua.ls Logo

Delta VFD007FP4EA-41 - Page 223

Delta VFD007FP4EA-41
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-01-2
Settings 0.0~480.0V
Mid-point Frequency 1 of Motor 2
Factory Setting: 3.00
Settings 0.00~599.00Hz
Mid-point Voltage 1 of Motor 2
Factory Setting: 22.0
Settings 0.0~480.0V
Mid-point Frequency 2 of Motor 1
Factory Setting: 1.50
Settings 0.00~599.00Hz
Mid-point Voltage 2 of Motor 1
Factory Setting: 10.0
Settings 460V series: 0.0~480.0V
Mid-point Frequency 2 of Motor 2
Factory Setting: 1.50
Settings 0.00~599.00Hz
Mid-point Voltage 2 of Motor 2
Factory Setting: 10.0
Settings 460V series: 0.0~480.0V
Min. Output Frequency of Motor 1
Factory Setting: 0.50
Settings 0.00~599.00Hz
Min. Output Voltage of Motor 1
Factory Setting: 2.0
Settings 0.0~480.0V
Min. Output Frequency of Motor 2
Factory Setting: 0.50
Settings 0.00~599.00Hz
Min. Output Voltage of Motor 2
Factory Setting: 0.0
Settings 0.0~480.0V
V/f curve setting is usually set by the motor’s allowable loading characteristics. Pay special
attention to the motor’s heat dissipation, dynamic balance, and bearing lubricity, if the loading
characteristics exceed the loading limit of the motor.
There is no limit for the voltage setting, but a high voltage at low frequency may cause motor
damage, overheat, and stall prevention or over-current protection. Therefore, please use the low
voltage at the low frequency to prevent motor damage.
Pr.01-35 to Pr.01-42 is the V/f curve for the motor 2. When multi-function input terminals
Pr.02-01~02-08 and Pr.02-26 ~Pr.02-31 are set to 14 and enabled, the AC motor drive will act as
the 2nd V/f curve.
The V/f curve for the motor 1 is shown as follows. The V/f curve for the motor 2 can be deduced

Table of Contents

Related product manuals