Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-02-1
02 Digital Input/Output Parameter This parameter can be set during operation.
2-wire/3-wire Operation Control
Factory Setting: 0
Settings 0: 2 wire mode 1
1: 2 wire mode 2
2: 3 wire mode
It is used to set the operation control method:
Pr.02-00 Control Circuits of the External Terminal
0
2-wire mode 1
FWD/STOP
REV/STOP
1
2-wire mode 2
RUN/STOP
REV/FWD
2
3-wire operation control
Multi-function Input Command 1 (MI1)
(MI1= STOP command when in 3-wire operation control)
Factory Setting: 1
Multi-function Input Command 2 (MI2)
Factory Setting: 2
Multi-function Input Command 3 (MI3)
Factory Setting: 3
Multi-function Input Command 4 (MI4)
Factory Setting: 4
Multi-function Input Command 5 (MI5)
Multi-function Input Command 6 (MI6)
Multi-function Input Command 7 (MI7)
Multi-function Input Command 8 (MI8)
Input terminal of I/O extension card (MI10)
Input terminal of I/O extension card (MI11)
Input terminal of I/O extension card (MI12)