Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-02-2
Input terminal of I/O extension card (MI13)
Input terminal of I/O extension card (MI14)
Input terminal of I/O extension card (MI15)
Factory Setting: 0
Settings
0: no function
1: multi-step speed command 1/multi-step position command 1
2: multi-step speed command 2/multi-step position command 2
3: multi-step speed command 3/multi-step position command 3
4: multi-step speed command 4/multi-step position command 4
5: Reset
6: JOG command (By KPC-CC02 or external control)
7: acceleration/deceleration speed not allow
8: the 1
st
, 2
nd
acceleration/deceleration time selection
9: the 3
rd
, 4
th
acceleration/deceleration time selection
10: EF Input (Pr.07-20)
11: B.B input from external (Base Block)
12: Output stop
13: cancel the setting of the optimal acceleration/deceleration time
14: switch between motor 1 and motor 2
15: operation speed command from AVI1
16: operation speed command from ACI
17: operation speed command from AVI2
18: Emergency stop (Pr.07-20)
19: Digital up command
20: Digital down command
21: PID function disabled
22: Clear counter
23: Input the counter value (MI6)
24: FWD JOG command
25: REV JOG command
26: Reserved
27: Reserved
28: Emergency stop (EF1)
29: Signal confirmation for Y-connection
30: Signal confirmation for Δ-connection
31~37: Reserved
38: Disable write EEPROM function
39: Reserved
40: Force coast to stop
41: HAND switch
42: AUTO switch
43~48: Reserved
49: Drive enable
50: Slave dEb action to execute
51: Selection for PLC mode bit0
52: Selection for PLC mode bit1
53: Trigger CANopen quick stop
54:
UVW Output Electromagnetic valve Switch
55: Brake release checking signal
56: Local/Remote Selection
57: Reserved
58: Enable fire mode (with RUN Command)
59: Enable fire mode (without RUN Command)
60: All motors disabled
61: Motor #1 disabled
62: Motor #2 disabled