Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-02-3
63: Motor #3 disabled
64: Motor #4 disabled
65: Motor #5 disabled
66: Motor #6 disabled
67: Motor #7 disabled
68: Motor #8 disabled
69: Preheating Command
This parameter selects the functions for each multi-function terminal.
The terminals of Pr.02-26~Pr.02-29 are virtual and set as MI10~MI13 when using with optional
card EMC-D42A. Pr.02-30~02-31 are virtual terminals.
When being used as a virtual terminal, it needs to change the status (0/1: ON/OFF) of bit 8-15 of
Pr.02-12 by digital keypad KPC-CC02 or communication.
If Pr.02-00 is set to 3-wire operation control. Terminal MI1 is for STOP contact. Therefore, MI1 is
not allowed for any other operation.
Summary of function settings (Take the normally open contact for example, ON: contact is closed,
OFF: contact is open)
Settings Functions Descriptions
0 No Function
1
Multi-step speed
command 1/ multi-step
position command 1
15 step speeds could be conducted through the digital status of the
4 terminals, and 16 in total if the master speed is included. (Refer to
Parameter set 4)
2
Multi-step speed
command 2/ multi-step
position command 2
3
Multi-step speed
command 3/ multi-step
position command 3
4
Multi-step speed
command 4/ multi-step
position command 4
5 Reset
After the error of the drive is eliminated, use this terminal to reset
the drive.
6 JOG Command
This function is valid when the source of operation command is
external terminals.
Before executing this function, it needs to wait for the drive stop
completely. During running, it can change the operation direction
and STOP key on the keypad is valid. Once the external terminal
receives OFF command, the motor will stop by the JOG
deceleration time. Refer to Pr.01-20~01-22 for details.
01-20
01 -2 1
ON
OFFMIx-GND
01-22
JO G fr eq ue ncy
01-07
Min. outp ut fr eq ue ncy
of motor 1
JOG accel. time
JOG decel. time