Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-02-5
Settings Functions Descriptions
14
Switch between drive
settings 1 and 2
When the contact of this function is ON: use motor 2 parameters.
OFF: use motor 1 parameters.
15
Operation speed
command form AVI
When the contact of this function is ON, the source of the frequency
will force to be AVI. (If the operation speed commands are set to
AVI1, ACI and AVI2 at the same time. The priority is AVI1ACI
AVI2)
16
Operation speed
command form ACI
When the contact of this function is ON, the source of the frequency
will force to be ACI. (If the operation speed commands are set to
AVI1, ACI and AVI2 at the same time. The priority is AVI1ACI
AVI2)
17
Operation speed
command form AUI
When the contact of this function is ON, the source of the frequency
will force to be AUI. (If the operation speed commands are set to
AVI1, ACI and AVI2 at the same time. The priority is AVI1ACI
AVI2)
18 Emergency Stop (07-20)
When the contact of this function is ON, the drive will ramp to stop
by Pr.07-20 setting.
19 Digital Up command
When the contact of this function is ON, the frequency will be
increased and decreased. If this function is constantly ON, the
frequency will be increased/decreased by Pr.02-09/Pr.02-10.
The frequency command returns to zero when the drive stops, and the
display frequency is 0.00Hz. Select Pr11-00, Bit7=1,
frequency is not
saved.
20 Digital Down command
21 PID function disabled
When the contact of this function is ON, the PID function is
disabled.
22 Clear counter
When the contact of this function is ON, it will clear current counter
value and display “0”. Only when this function is disabled, it will
keep counting upward.
23
Input the counter value
(multi-function input
command 6)
The counter value will increase 1 once the contact of this function is
ON. It needs to be used with Pr.02-19.
24 FWD JOG command
When the contact is ON, the drive will execute forward Jog
command.
25 REV JOG command
When the contact is ON the drive will execute reverse Jog
command.
26
Reserved
27
Reserved
28
Emergency stop (EF1)
When the contact is ON, the drive will execute emergency stop and
display EF1 on the keypad. The motor won’t run and be in the free
run until the fault is cleared after pressing RESET” (EF: External
Fault)
ON
MI -GNDx
ON
OFF
ON
Reset
ON
OFF
Voltage
Fr eq ue ncy
Setting
fr eq ue ncy
Time
Operation
command