Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-02-6
Settings Functions Descriptions
29
Signal confirmation for
Y-connection
When is the contact of this function is ON, the drive will operate by
1st V/f.
30
Signal confirmation for
Δ-connection
When the contact of this function is ON, the drive will operate by
2nd V/f.
31~37
Reserved
38
Disable EEPROM write
function
(Parameters written
disable)
When the contact of this function is ON, write to EEPROM is
disabled. (Changed parameters will not be saved after power off)
39 Reserved
40
Force coast to stop
When the contact of this function is ON during the operation, the
drive will free run to stop.
41
HAND switch
1. When MI is switched to off status, it executes a STOP
command. , If MI is switched to off during operation, the drive
will also stop.
2. Using keypad KPC-CC01 to switch between HAND/AUTO,
the drive will stop first then switch to the HAND or AUTO status.
3. On the digital keypad KPC-CC01, it will display current drive
status (HAND/OFF/AUTO).
Bit 1 Bit 0
OFF 0 0
AUTO 0 1
HAND 1 0
OFF 1 1
42
AUTO switch
43~48
Reserved
49 Drive enable
When drive=enable, RUN command is valid.
When drive= disable, RUN command is invalid.
When drive is in operation, motor coast to stop.
This function will interact with MO=51
50
Slave dEb action to
execute
Input the message setting in this parameter when dEb occurs to
Master. This will ensure dEb also occurs to Slave, then Master and
Slave will stop simultaneously.
51
Selection for PLC mode
bit0
PLC status Bit 1 Bit 0
Disable PLC function (PLC 0) 0 0
Trigger PLC to operation (PLC 1) 0 1
Trigger PLC to stop (PLC 2) 1 0
No function 1 1
52
Selection for PLC mode
bit1
53
Enable CANopen quick
stop
When this function is enabled under CANopen control, it will
change to quick stop. Refer to Chapter 15 for more details.
54
UVW magnetic contactor
ON/OFF
To receive confirmation signals while there is UVW magnetic
contactor during output.
55
Brake release checking
signal
This parameter needs to be used with P02-56. The main purpose is
to make sure if mechanical brake works or not after triggering brake
release command.
If the action is right, mechanical brake will give signal to MI
terminal.
Please check time sequence chart for reference.