Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-02-7
Settings Functions Descriptions
56
LOCAL/REMOTE
Selection
Use Pr.00-29 to select for LOCAL/REMOTE mode (refer to
Pr.00-29).
When Pr.00-29 is not set to 0, on the digital keypad KPC-CC01 it
will display LOC/REM status. (It will display on the KPC-CC01 if the
firmware version is above version 1.021).
Bit 0
REM 0
LOC 1
57
Reserved
58
Enable fire mode with
RUN Command
Enable this function under fire mode to force the drive to run (while
there is RUN COMMAND).
59
Enable fire mode
without RUN Command
Enable this function under fire mode to force the drive to run (while
there isn’t RUN COMMAND).
60 Disable all the motors
When the multi-motor circulative control is enable, all motors will
park freely, when the function terminal set to be ON.
61 Disable Motor#1 These functions work with multi-motor circulative control, motor #1
to # 8 can be set to park freely. If any of Auxiliary Motor#1 to
Motor#8 is out of order or under maintenance, enable this terminal
to bypass that motor.
62
Disable Motor#2
63
Disable Motor#3
64
Disable Motor#4
65
Disable Motor#5
66 Disable Motor#6
67 Disable Motor#7
68
Disable Motor#8
69 Preheating Command
When the function terminal is setting to ON, if the preheating
function is open and drive is in STOP status, the preheating
function is executed; until the contact status (OFF) or drive status is
turned to RUN, the preheating function is stop. Please refer to
Pr.02-72~73 for detail.
UP/DOWN Key Mode
Factory Setting: 0
Settings 0: Up/down by the accel/decel time
1: Up/down constant speed (Pr.02-10)
Constant speed. The Accel. /Decel. Speed of the UP/DOWN Key
Factory Setting: 0.001
Settings 0.001~1.000Hz/ms
These settings are used when multi-function input terminals are set to 19/20. Refer to Pr.02-09
and 02-10 for the frequency up/down command.
Pr11-00, Bit7=1, frequency command is not saved. The frequency command returns to zero
when the drive stops, and the display frequency is 0.00Hz. The frequency command