Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-02-22
Factory Setting: Read only
Settings 0.01~599.00Hz (Read only)
When the source of frequency command comes from the external terminal, if Lv or Fault occurs
at this time, the frequency command of the external terminal will be saved in this parameter.
Reserved
Reserved
IO Card Type
Factory setting: Read only
Settings Read only
0: No IO Card
1: EMC-BPS01 Card
2: No IO Card
3: No IO Card
4: EMC-D611A Card
5: EMC-D42A Card
6: EMC-R6AA Card
7: No IO Card
Output Current Level of Preheating
Factory Setting: 0
Settings 0~100%
When a motor drive is not in operation (STOP) and is placed in a cold and humid environment,
enable the preheating function to output DC current to heat up the motor drive can prevent the
invasion of the humidity to the motor drive which creates condensation affecting the normal
function of the motor drive.
This parameter sets the output current level from the motor drive to the motor after enabling the
preheating. The percentage of the preheating DC current is 100% to the rated current of the
motor drive (Pr.05-01, Pr.05-13, Pr.05-34). When setting this parameter, increase slowly the
percentage to reach the sufficient preheating temperature.
Output Current Cycle of Preheating
Factory Setting: 0
Settings 0~100%
This parameter sets the output current cycle of preheating. 0 ~100% corresponds to 0~10
seconds. When set to 0%, there is no output current. When set to 100%, there is a continuous
output. For example, when set to 50%, a cycle of preheating goes from OFF(5 seconds) to
ON(5 seconds) and vice versa.
Related Parameters of Preheating