Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-06-27
Code Error name
Normal
mode
Fire Mode
Enable bypass
function
74
Fire Mode output V V(keeps on
operating)
V(keeps on
operating)
76 Safety Torque Off (STO) V Not-detectable Not-detectable
77
Channel 2 (STO2~SCM2) internal
hardware error (STL2)
V Not-detectable Not-detectable
78
Channel 1 and Channel 2 internal
hardware error (STL3)
V Not-detectable Not-detectable
79 U phase over current (Uocc) V V(able to auto-reset) V
80 V phase over current (Vocc) V V(able to auto-reset) V
81 W phase over current (Wocc) V V(able to auto-reset) V
82 OPHL U phase output phase loss V V(able to auto-reset) V
83 OPHL Vphase output phase loss V V(able to auto-reset) V
84 OPHL Wphase output phase loss V V(able to auto-reset) V
90 Inner PLC function is forced to stop V Not-detectable Not-detectable
99 CPU Trap error V V Not-detectable
101 CGdE CANopen software disconnect1 V Not-detectable Not-detectable
102 CHbE CANopen software disconnect2 V Not-detectable Not-detectable
103 CSYE CANopen synchronous error V Not-detectable Not-detectable
104 CbFE CANopen hardware disconnect V Not-detectable Not-detectable
105 CIdE CANopen index setting error V Not-detectable Not-detectable
106
CAdE CANopen slave station number
setting error
V Not-detectable Not-detectable
107
CFrE CANopen index setting exceed
limit
V Not-detectable Not-detectable
111
InrCOM Internal communication
overtime error
V Not-detectable Not-detectable
Fire mode motion
Factory Setting: 0
Settings
0:
Open loop control & manual reset fire mode
1: Close loop control & manual reset fire mode
2: Open loop control & auto reset fire mode
3: Close loop control & auto reset fire mode
Fire mode PID set point
Factory Setting: 0.0
Settings 0~100.00% (according to Pr.01-00 Max. operation frequency)