EasyManua.ls Logo

Delta VFD007FP4EA-41 - Page 365

Delta VFD007FP4EA-41
404 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-12-1
12 Pump Parameters
This parameter can be set during operation.
Circulative Control
Factory Setting: 0
Settings 0: No operation
1: Fixed Time Circulation (by time)
2: Fixed Quantity
3: Fixed quantity control
4: Fixed Time Circulation + Fixed Quantity Circulation
5: Fixed Time Circulation + Fixed Quantity Control
In this mode, CFP2000 can control up to 8 motors at a time. The total number of the motors can
be determined by Pr.12-01. In accordance with the Fixed Time Circulation of Pr12-02, you can
adjust the switching time between Start/Stop of each motor. That means when an operating motor
reaches the time setting of Pr12-02, CFP2000 will stop that motor. Then after the delay time
setting of Pr12-03, next motor will start operating. See diagram below.
Diagram 12-1: Sequential Diagram of the Fixed Time Circulation (by time)
Disable Motors’ Output
Set the Multifunction Input Commands as Disable Motors’ Output can stop corresponding
motors. The settings are:
P02-01~P02-06= 60 61 62 63 64 65 66 67 68
Disable Motors’ Output ALL 1 2 3 4 5 6 7 8
When a motor’s output is disabled, this motor will park freely.

Table of Contents