Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-13-3
4: Pump
Pr Explanation Settings
00-11
Control of Speed Mode
0(VF)
00-16
Load Selection
1: Normal load
00-20
Carrier Frequency
2: External analog input (Pr.03-00)
00-21
Source of Master Frequency
Command(AUTO)
1: External terminals. Keypad STOP disabled.
00-23
Source of the Operation
Command (AUTO)
1: Reverse disable
01-00
Max. Operation Frequency
60.00/
50.00
01-01
Output Frequency of Motor 1
60.00/
50.00
01-02
Output Voltage of Motor 1 400.0
01-03
Mid-point Frequency 1 of Motor
1
3.00
01-04
Mid-point Voltage 1 of Motor 1 22.0
01-05
Mid-point Frequency 2 of Motor
1
1.50
01-06
Mid-point Voltage 2 of Motor 1 10.0
01-07
Min. Output Frequency of Motor
1
0.50
01-08
Min. Output Voltage of Motor 1 2.0
01-10
Output Frequency Upper Limit
50(Hz)
01-11
Output Frequency Lower Limit
35(Hz)
01-12
Accel. Time 1
15(s)
01-13
Decel Time 1
15(s)
01-43 V/f Curve Selection 2: 2
nd
V/F curve
07-06
Restart after Momentary Power
Loss
2: Speed search for minimum output frequency
07-11
Number of Times of Auto Restart
After Fault
5
07-33 Auto restart internal of Fault 60(s)
~
Application Parameter 1~99