Chapter 11 Summary of Parameter SettingsMS300 (High Speed Model)
11-3
Pr. Explanation Settings
Factory
Setting
00-05
Coefficient gain in actual
output frequency
0~160.00 1.00
00-06
Software version Read only
#.#
00-07
Parameter protection
password input
0~65535
0~3 (the times of password attempts)
0
00-08
Parameter protection
password setting
0~65535
0: No password protection / password is entered correctly
(Pr. 00-07)
1: Password has been set
0
00-10 Control mode
0: Speed mode
Read
Only
00-11 Control of speed mode
0: VF (IM V/F control)
Read
Only
00-16 Load selection 1: Heavy load
Read
Only
00-17 Carrier frequency Heavy load: 2~15 KHz 6
00-19 PLC command mask
bit 0: Control command forced by PLC control
bit 1: Frequency command forced by PLC control
Read
Only
00-20
Source of the master
frequency command (AUTO)
0: Digital keypad
1: Communication RS-485 input
2: External analog input (Refer to Pr. 03-00)
3: External UP / DOWN terminal
6: CANopen communication card
7: Digital keypad dial
8: Communication card
(not includes CANopen card)
[Note]:
Need to use with MO setting as 42, or use with KPC-CC01
0
00-21
Source of the operation
command (AUTO)
0: Digital keypad
1: External terminals
2: Communication RS-485 input
3: CANopen communication card
5: Communication card (not includes CANopen card)
[Note]:
Need to use with MO setting as 42, or use with KPC-CC01
0
00-22 Stop method
0: Ramp to stop
1: Coast to stop
0
00-23 Control of motor direction
0: Enable forward / reverse
1: Disable reverse
2: Disable forward
0