Chapter 11 Summary of Parameter SettingsMS300 (High Speed Model)
11-25
Pr. Explanation Settings
Factory
Setting
06-67
Operation time of fault record 3
(Day)
0~65535 days
Read
only
06-68
Operation time of fault record 3
(Min.)
0~1439 min.
Read
only
06-69
Operation time of fault record 4
(Day)
0~65535 days
Read
only
06-70
Operation time of fault record 4
(Min.)
0~1439 min.
Read
only
06-71 Low current setting level 0.0 ~ 100.0 % 0.0
06-72 Low current detection time 0.00 ~ 360.00 sec. 0.00
06-73 Treatment for low current
0 : No function
1 : Warn and coast to stop
2 : Warn and ramp to stop by 2
nd
deceleration time
3 : Warn and operation continue
0
06-90
Operation time of fault record 5
(Day)
0~65535 days
Read
only
06-91
Operation time of fault record 5
(Min.)
0~1439 min.
Read
only
06-92
Operation time of fault record 6
(Day)
0~65535 days
Read
only
06-93
Operation time of fault record 6
(Min.)
0~1439 min.
Read
only