Chapter 11 Summary of Parameter SettingsMS300 (High Speed Model)
11-26
07 Special Parameters
Pr. Explanation Settings
Factory
Setting
07-00 Software brake level
230 V: 350.0~450.0 VDC
460 V: 700.0~900.0 VDC
370.0
740.0
07-01 DC brake current level
0~100 %
0
07-02 DC brake time at startup
0.0~60.0 sec.
0.0
07-03 DC brake time at stop 0.0~60.0 sec. 0.0
07-04 DC brake start frequency
0.0~1500.0 Hz
0.0
07-05 Voltage increasing gain
1~200 %
100
07-06
Restart after momentary power
loss
0: Stop operation
1: Speed tracking by the speed before the power loss
2: Speed tracking by minimum output frequency
0
07-07 Allowed power loss duration
0.0~20.0 sec.
2.0
07-08 Base block time
0.1~5.0 sec.
0.5
07-09 Current limit of speed tracking 20~200 %
100
07-10 Treatment of restart after fault
0: Stop operation
1: Speed tracking by current speed
2: Speed tracking by minimum output frequency
0
07-11
Restart times after fault 0~10
0
07-12 Speed tracking during start-up
0: Disabled
1: Speed tracking by maximum output frequency
2: Speed tracking by motor frequency at start
3: Speed tracking by minimum output frequency
0
07-13 dEb function selection
0: Disabled
1: dEb with auto accel. / decal., the frequency will not
return after power recovery
2: dEb with auto accel. / decal., the frequency will
return after power recovery
0
07-15 Dwell time at accel.
0.00 ~ 600.00 sec.
0.00
07-16 Dwell frequency at accel. 0.0~1500.0 Hz 0.0
07-17 Dwell time at decel.
0.00 ~ 600.00 sec.
0.00
07-18 Dwell frequency at decel.
0.0~1500.0 Hz
0.0
07-19 Fan cooling control
0: Fan always ON
1: Fan will be OFF after the AC motor drive stops 1
minute
2: When the AC motor drive runs, the fan is ON. When
the AC motor drive stops, the fan is OFF
3: Fan turns ON when the temperature attain around
60
o
C
3