Chapter 11 Summary of Parameter SettingsMS300 (High Speed Model)
11-28
09 Communication Parameters
Pr. Explanation Settings
Factory
Setting
09-00
Communication address
1~254
1
09-01
COM1 transmission speed
4.8~115.2 Kbps
9.6
09-02
COM1 transmission fault treatment
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
3
09-03
COM1 time-out detection
0.0~100.0 sec.
0.0
09-04 COM1 communication protocol
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
1
09-09
Delay time of communication
response
0.0~200.0 ms
2.0
09-10
Main frequency of the
communication
0.0~1500.0 Hz
600.0
09-11 Block transfer 1 0~65535 0
09-12
Block transfer 2
0~65535
0
09-13
Block transfer 3
0~65535
0
09-14 Block transfer 4 0~65535 0
09-15
Block transfer 5
0~65535
0
09-16
Block transfer 6
0~65535
0
09-17 Block transfer 7 0~65535 0
09-18
Block transfer 8
0~65535
0
09-19
Block transfer 9
0~65535
0
09-20 Block transfer 10 0~65535 0

Table of Contents