EasyManuals Logo

Delta VFD9A0MS43ANSHA User Manual

Delta VFD9A0MS43ANSHA
445 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #335 background imageLoading...
Page #335 background image
Chapter 16 PLC Function ApplicationsMS300 (High Speed Model)
16-4
8. When Pr. 00-04 is set as 28, the displayed value will be the value of PLC register D1043 (see
figure below):
Digital Keypad KPC-CC01 (optional)
Can display 0~65535
H 0.00Hz
A 0. 00H z
C _ _ _ _ _
9. In the PLC Run and PLC Stop mode, the content 9 and 10 of Pr. 00-02 cannot be set and cannot
be reset to the default value.
10. The PLC can be reset to the default value when Pr. 00-02 is set as 6.
11. The corresponding MI function will be disabled when the PLC writes to input contact X.
12. When the PLC controls drive operation, control commands will be entirely controlled by the PLC
and will not be affected by the setting of Pr. 00-21.
13. When the PLC controls drive frequency commands (FREQ commands), frequency commands
will be entirely controlled by the PLC, and will not be affected by the setting of Pr. 00-20 or the
Hand ON/OFF configuration.
14. When the PLC controls drive operation, if the keypad Stop setting is valid, this will trigger
an FStP error and cause stoppage.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD9A0MS43ANSHA and is the answer not in the manual?

Delta VFD9A0MS43ANSHA Specifications

General IconGeneral
BrandDelta
ModelVFD9A0MS43ANSHA
CategoryController
LanguageEnglish

Related product manuals