79
DC Outputs
Output 1 Accuracy: mA: 0 - 20mA ± 0.5% of span (20 mA) @250 ohm
4 - 20mA ± 0.5% of span (16 mA) @ 250 ohm
V: 0 - 10V ± 0.5% of span (10 V) @ 2K ohm
0 - 5V ± 0.5% of span (5 V) @ 2K ohm
Output 2 Accuracy: mA: 0 - 20mA ± 0.5% of span (16 mA) @250 ohm
4 - 20mA ± 0.5% of span (16 mA) @ 250 ohm
V: 0 - 10V ± 0.5% of span (10 V) @ 2K ohm
0 - 5V ± 0.5% of span (5 V) @ 2K ohm
Output 3 Accuracy: mA: 0 - 20mA ± 0.5% of span (20 mA) @250 ohm
(Recorder Accuracy) 4 - 20mA ± 0.5% of span (16 mA) @ 250 ohm
V: 0 - 10V ± 0.5% of span (10 V) @ 2K ohm
0 - 5V ± 0.5% of span (5 V) @ 2K ohm
Operating Conditlons
Ambient Operating
Temperature: 0º to 55º C
Ambient Storage
Temperature: -20º to 80º C
Relative Humidity: 20% - 95% non-condensing
Supply Voltage: 90 - 264 VAC 50/60 Hz (standard)
20 - 50 VAC 50/60 Hz or 22 - 65 VDC (option)
Source Resistance: 1000 ohms maximum (thermocouple)
Lead Resistance: 50 ohms per lead maximum balanced (Pt100)