75
To Select Remote Setpoint/
Setpoint 1:
Minimum contact resistance (open): 5K ohms
Minimum voltage for (TTL) for " 1 ": 2.0 V
Maximum voltage for "1”: 24.0 V
Maximum input delay (OFF-ON): 0.5 seconds
Minimum input delay (ON-OFF): 0.5 seconds
Isolation: 240 VAC isolation from all setpoints and
inputs except Remote Setpoint
Output Specifications
Output 1
General
Types Available: Relay (as standard), SSR Driver and DC as options.
Relay
Contact Type: Single pole double throw SPDT
Rating: 2A resistive at 120/240V AC
Lifetime: > 500,000 operations at rated voltage/current
Isolation: Inherent
SSR Driver/TTL
Drive Capability: SSRD>4.3V DC into 250 ohm minimum
Isolation: Not isolated from input or other SSR outputs.
DC Resolution: Eight bits in 250mS (10 bits in 1 second typical, >10 bits in
>1 second typical).
Update Rate: Every control algorithm execution
Ranges: 0 - 20 mA, 4 - 20 mA, 0 - 10V, and 0 - 5 V
NOTE: Changes between V and mA ranges also require JU movement.
Load Impedance: 0-20 mA: 500 ohm maximum
4 - 20 mA: 500 ohm maximum
0 - 10 V: 500 ohm minimum
0 - 5V: 500 ohm minimum
Isolation: Isolated from all other inputs and outputs.