FIRE ALARM PANEL
X3301 DETECTOR
SHIELD
ALARM
24 VDC
+
–
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL o
i
TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
EOL
RESISTOR
4
o
i
TEST
3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE
2
COM FIRE
NO FIRE
2
NO FIRE
NC FIRE
2
NC FIRE
COM FAULT
1
COM FAULT
NO FAULT
1
N.O. FAULT
+Vin
–Vin
+Vin
–Vin
–Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS485 A
RS485 B
MAN O
i
mA +
mA –
mA + REF mA – REF
COM AUX
NO AUX
NC AUX
E2109
FIRE ALARM PANEL
X3301 DETECTOR
ALARM
ALARM
24 VDC
+
–
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL o
i
TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 EOL RESISTOR SUPPLIED BY PANEL.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
EOL
RESISTOR
4
o
i
TEST
3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE
2
COM FIRE
NO FIRE
2
NO FIRE
NC FIRE
2
NC FIRE
COM FAULT
1
COM FAULT
NO FAULT
1
NO FAULT
+Vin
–Vin
+Vin
–Vin –Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS485 A
RS485 B
MAN O
i
mA + mA –
mA + REF
mA – REF
COM AUX
NO AUX
NC AUX
SHIELD
Figure7—Ex d Wiring Option
Figure8—Ex d e Wiring Option